Phoenix Contact QUINT4-UPS/24DC/24DC/10 Uninterruptible Power Supply

QUINT UPS, IQ Technology, DIN rail mounting, Screw connection, input: 24 V DC, output: 24 V DC / 10 A, charging current: 3 A

The intelligent QUINT UPS for integration into established industrial networks: your systems continue to be supplied with uninterrupted power, even in the event of a mains failure. The battery management system with IQ Technology and a powerful battery charger ensures superior system availability.

Input Data
Input voltage24 V DC
Input voltage range18 V DC ... 30 V DC
Electric strength, max.35 V DC (Protected against polarity reversal)
Internal input fuseno
Typical national grid voltage24 V DC
Voltage type of supply voltageDC
Inrush current≤ 7 A (≤ 4 ms)
Reverse polarity protectionyes
Fixed backup threshold22 V DC
30 V DC
Dynamic activation threshold> 1 V / 100 ms
Switch-on timemax. 3 s
Switch-on time during battery operation (Bat.-Start)8 s
Voltage drop, input/output0.4 V DC
Current consumption IN (UN, IOUT = IN, Icharge = 0)10.1 A
Current consumption Imax (UN, IOUT = IStat.Boost, ICharge = max)16.2 A
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0)48 mA
Current consumption Icharge (UN, IOUT = 0, Icharge = max)3.5 A
Power consumption PN (UN, IOUT = IN, Icharge = 0)241 W
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max)384 W
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0)1.2 W
Power consumption Pcharge (UN, IOUT = 0, Icharge = max)90 W
Signal state Bat.-Start
Connection labeling3.8 (+)
ChannelDI (digital input)
StateBat.-Mode
State conditionLow level (30 ms)
Low signalInput connected with SGnd (3.9) or Bat
High signalInput not connected or connected with >UBat
Signal - state assignmentlow - active
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)
LED status indicatorYellow (Bat.-Mode)
Signal state PS Boost
Connection labeling3.7 (+)
Channel (configurable)DI (digital input) default, AI (analog input)
State (configurable)Charging current reduced
State conditionLow level
Low signalInput connected with SGnd (3.9), <5 V DC or not connected
High signalInput connected with 13 … 30 V DC
Signal - state assignmentlow - active
Analog4 mA ... 20 mA (Offset zero point)
Unit signalI (mA)
Load390 Ω
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)
Signal state Remote
Connection labeling3.6 (+)
ChannelDI (digital input)
State (configurable)Disconnection
State conditionLow level
Low signalInput connected with SGnd (3.9) or <5 V DC
High signalInput not connected or connected with 13 … 30 V DC