Description
CyberPower OLS2000ERT2UA Online S 2000VA/1800W RACK UPS
CyberPower OLS2000ERT2U is a high-performance UPS featuring online double-conversion topology, which provides seamless Pure Sine Wave power for mission-critical devices such as NAS and servers, DVRs/surveillance systems, transportation and infrastructure, and emergency systems. It's typically integrated in the back office, server room, and data center environment.
- Online (Double Conversion) UPS Topology
- ECO Mode
- Generator Compatible
- Overload Protection Zero Transfer Time
- Smart Battery Management (SBM)
- Extended Battery Module (EBM)
- Surge and Spike Protection
- EMI and RFI Filtration
- Phone/Fax/Modem/DSL/Network Protection
- LCD Status Display
- Emergency Power Off (EPO) Port
- PowerPanel® Management Software
- SNMP/HTTP Remote Management Capability (Optional)
- Rack/Tower Convertible Configurations
General
Phase
Single Phase
UPS Topology
Online Double Conversion
Energy Saving Technology
Online ECO Mode Efficiency > 95%
Active PFC Compatibility
Yes
Input
Generator Compatibility
Yes
Nominal Input Voltage ( Vac )
230 ± 10%
Input Voltage Range ( Vac )
160 ~ 300
Adjustable Voltage Range ( Vac )
0~50% Load for 110 ~ 300 Vac
0~60% Load for 120 ~ 300 Vac
0~80% Load for 140 ~ 300 Vac
0~100% Load for 160 ~ 300 Vac
Input Frequency ( Hz )
50 ± 10
60 ± 10
Input Frequency Detection
Auto-sensing
Rated Input Current ( A )
9
Input Power Factor
0.98
Input Connector Type
IEC C20
Plug Style
Straight
Detachable Power Cord Plug Type
AU x 1
Power Cord Length (ft.)
5.9
Power Cord Length (m.)
1.8
Output
Capacity (VA)
2000
Capacity (Watts)
1800
On Battery Waveform
Pure Sine Wave
On Battery Voltage(s) ( Vac )
208 ± 1%
220 ± 1%
230 ± 1%
240 ± 1%
Output Voltage Setting
Configurable
On Battery Frequency ( Hz )
50 ± 0.5%
60 ± 0.5%
Output Frequency Setting
Configurable
Power Factor
0.9
ECO Mode Voltage Tolerance
± 15 %
Overload Protection
Internal Current Limiting , Circuit Breaker , Fuse
Overload Protection (Line Mode)
110~120% Load for 1 min, >120% Load Immediately
Overload Protection (Battery Mode)
110~120% Load for 10 sec, >120% Load Immediately
Overload Protection (Bypass Mode)
>130% Load Immediately
Crest Factor
3 : 1
Harmonic Distortion (Linear Load)
THD<3%
Harmonic Distortion (Non-linear Load)
THD<5%
Internal Bypass
Automatic Bypass , Manual Bypass
Outlet(s) - Total
8
Outlet Type
IEC C13 x 8
Outlet(s) - Battery & Surge Protected
8
Typical Transfer Time ( ms )
0
Battery
Runtime at Half Load ( min )
15
Runtime at Full Load ( min )
5
Typical Recharge Time ( Hours )
5
Maximum Charging Current ( A )
1
Start On Battery
Yes
Smart Battery Management (SBM)
Yes
User-replaceable
Yes
View AllClose
Additional Information
Stock Available Onehunga: |
0 |
Stock Available St Lukes: |
0 |
Stock Available Wellington: |
0 |
Stock Available Supplier: |
0 |